The maximum coverage per sprinkler head shall be limited to 80 ft 2 (7.4 m 2).The following design and installation guides shall apply where pendent sprinklers in the upright position or old-style sprinklers are to be utilized: * The supply line to the duct sprinklers, if taken from the ceiling sprinkler system, shall be equipped with an accessible listed control valve.* The system demand shall include the discharge from the hydraulically most remote adjacent sprinklers in a common 100 linear ft (30.5 m) area of duct (horizontal and/or vertical).Sprinklers shall be ordinary temperature rated, unless required to be higher due to operating temperatures measured in the ducts, in which case the operating temperature shall be at least 50☏ (28☌) above the inside temperature of the duct.Sprinklers shall provide a minimum flow of 30 gpm (114 L/min) per head at a minimum of 15 psi (1 bar) pressure.If exhaust ducts are manifolded, a sprinkler shall be located in the manifold at the junction of each exhaust duct with the manifold.Horizontal exhaust ducts shall have sprinklers located on 12 ft (3.7 m) centers beginning no more than 6 ft (1.7 m) from the duct entrance.Additional sprinklers shall be spaced on 24 ft (7.3 m) centers if the rise is greater than 24 ft (7.3 m). One sprinkler shall be located at the top of each vertical riser and at the midpoint of each offset. (0.25 m) but less than 12 ft (3.7 m) shall meet all of the following requirements: Sprinkler systems protecting stacks or ducts with widths or diameters equal to or greater than 10 in.